Protecting back up power for Facilities Management
IPU were called to a critical data centre near Chester after a critical power failure. During a power cut its generators stopped running after just 4 minutes. After investigation the client discovered water in their fuel tanks. Challenges faced A high water table and heavy rainfall meant the fuel tank manhole was full of water. This overwhelmed the sump pump and allowed water to enter the tank via a sheared dip cap. High levels of groundwater were also identified in the tank and diesel was visible in the flooded manhole. This meant the facility posed a serious environmental risk. Solutions delivered Thankfully, IPU’s Fuel Team attended the site and removed 9,000 litres of water and…